FR8NM 6kA RCCB Electromagnetic Type
-
Precise Leakage Protection
- Rated residual current from 10mA to 500mA
- Sensitivity to type A, AC, SI residual current
- Time characteristic of type A, AC, G, and S
-
Higher Performance
- Wide range of rated current from 25A to 100A
- Conditional short circuit current of 6kA
- Electromagnetic type, high immunity to interference
-
Simplified Installation and Testing
- Busbar and cable connections, meets flexible wiring needs
- Clear indication window and an easy handle lock
- Intuitive test button, enable quick testing and maintenance
Tech Specs
| GENERAL | SHORT CIRCUIT | |||
| Poles | 2P, 4P | Conditional short circuit strength | 6kA | |
| Rated current | 25-100A | |||
| Rated operational voltage | 230/400V AC | RESIDUAL CURRENT | ||
| Rated frequency | 50/60Hz | Rated residual current | 10-500mA | |
| Rated insulated voltage | 500V AC | Residual current protection type | Electromagnetic | |
| Dielectric test voltage | 2.5kV | Min.voltage for RCD function | Independent of voltage | |
| Voltage range of the test button T | 150 - 253V AC (2P) / 150 - 440V AC (4P) | Sensitivity to residual current | A type, AC type, SI type | |
| Mechanical service life | 10000 | Time characteristic | AC, A - Undelayed type G - delay (insensitivity) 10 - 300 ms S - delay (insensitivity) 130 - 500 ms | |
| Electrical service life | 4000 | |||
| COMPLIANCE | ||||
| International standard | IEC/EN 61008-1 |
Download

FAQs
-
1. Electromagnetic vs. Electronic RCCB?
Electromagnetic RCCBs offers simple construction, fast response and greater inherent immunity to certain high-frequency EMI; Electronic RCCBs supply advanced features (time delay, diagnostics, adjustable sensitivity) but rely on electronic sensing that may require filtering or EMI mitigation in noisy environments.
-
2. Will it nuisance-trip and how to reduce it?
-
3. Lifespan, maintenance and test frequency?