Rated Range & Standards
- Rated current options up to 25 A, 40 A, 63 A, and 100 A
- Complies with IEC/EN 61095
- Suitable for dependable low-voltage switching applications
-
Voltage & Application Scope
- HC-225 / HC-240 / HC-263: Ue = 230 V~
- HC-425 / HC-440 / HC-463: Ue = 400 V~
- Utilization categories: AC-1, AC-7a, and AC-7b
-
Operating Window & Control Stability
- Ui: 500 V for strong insulation performance
- Contactor pulls in reliably at 85% to 110% of Us
- Contactor releases fully at 75% to 200% of Us
Tech Specs
| Appointed Operation Performance | ||||||
| Utilization Category | Ic/Ie | Ur/Ue | cosΦ | making times | interval times | operation cycle times |
| AC-7a | 1.0 | 1.05 | 0.80 | 0.05 | 10 | 30000 |
| AC-7b | (c) | (b) | 0.45 | 0.05 | 10 | 30000 |
| (a) If contact has closed completely before breaking again, the making time is allowed less than 0.05s. (b) For making operation Ur/Ue=1.0, for breaking operation Ur/Ue=0.17. (c) For making operation Ie/Ic=6.0, for breaking operation Ie/Ic=1.0. |
||||||
| Making and Breaking Capacity | ||||||
| Utilization Category | Ic/Ie | Ur/Ue | cosΦ | making times | interval times | operation cycle times |
| AC-7a | 1.5 | 1.05 | 0.80 | 0.05 | 10 | 50 |
| AC-7b | 8.0 | 1.05 | 0.45 | 0.05 | 10 | 50 |