Tech Specs
| GENERAL | SHORT CIRCUIT | |||
| Poles | 3P, 4P | Breaking capability level | S | H |
| Shell frame maximum rated current | 1600A | Limit breaking capacity | 50kA(AC415V,AC500V) 10kA(AC690V) |
65kA(AC415V) 50kA(AC500V) 15kA(AC690V) |
| Rated current | 800-1600A | Running breaking capacity | 50kA(AC415V,AC500V) 10kA(AC690V) |
65kA(AC415V) 50kA(AC500V) 15kA(AC690V) |
| Rated voltage | AC415/500/690 | Type of trip unit | Electronic type | |
| Rated insulated voltage | 1000V | OTHERS | ||
| Flying arc Distance | 0mm | Working with categories | B | |
| Mechanical life test | 10000 | COMPLIANCE | ||
| Electrical life test | 1500(AC415V) 1000(AC690V) |
International standard | IEC60947-2 | |
Download

PN.pdf
FAQs
-
Q1:Is the PN Series MCCB suitable for compact installations?
-
Q2:How easy is it to maintain the PN Series MCCB?
-
Q3:Are environmentally conscious materials used in the PN Series MCCB?